Water Cooled Screw Chiller ( AGS-W )
- Company Name:Shenzhen Anges machinery Co., Ltd
- Membership:Free Member
- Member Since:2009. 06.16
- Country/Region:China
- City:Guangdong
- Contact:Colin Liao
- Related Keywords:chiller, screw type, industial, refrigeration
Shenzhen Anges machinery Co., LtdContact us
Shenzhen Anges machinery Co., Ltd
[China]
Controlled operating system for ANGES screw type water chiller:
The controlled operating system is applied imported PLC program-controller.The man-machine interface is a big LED touch screen,which achieves intelligent man-machine diaglogue.A large number of fault solutions and technical data are stored in the system ,thus it is much convenient to operate and maintain the chiller unit.
Technical data for AGS-W series from AGS-085WDH ~ AGS-170WD
|
Model |
AGS-085WDH |
AGS-100WDH |
AGS-120WDH |
AGS-150WDH |
AGS-170WDH |
|
|
Item |
||||||
|
nominal cooling capacity |
kcal/h |
202960 |
258000 |
301000 |
395600 |
455800 |
|
kw |
236 |
300 |
350 |
460 |
530 |
|
|
input power |
kw |
60 |
72 |
82 |
112 |
121 |
|
max. running current |
A |
142 |
168 |
192 |
262 |
284 |
|
power supply |
3PH~380V 50HZ |
|||||
|
refrigerant |
type |
R22 /R407c |
||||
|
refrigerating circuit |
2 |
|||||
|
type of control |
thermostatic expansion valve |
|||||
|
compressor |
type |
semi-hermetic screw |
||||
|
quantity |
2 |
|||||
|
start-up mode |
Y- â³ |
|||||
|
capacity control |
0-25-50-75-100 |
|||||
|
condenser |
type |
shell and tube |
||||
|
evaporator |
type |
shell and tube |
||||
|
quantity |
1 |
|||||
|
chilled fluid flow(m 3 /h) |
41 |
52 |
60 |
79 |
91 |
|
|
safety protection |
compressor over temperature, unit overload, high and low pressure, flow switch, phase sequence, phase-missing, antifreezing |
|||||
|
net weight |
kg |
1800 |
2100 |
2400 |
2800 |
3100 |
|
running weight |
kg |
2050 |
2450 |
2700 |
3100 |
3500 |
|
Note: 1. nominal cooling capacity is according to: |
||||||
|
Inlet chilled fluid temperature: 12â.Outlet chilled fluid temperature: 7â. |
||||||
|
Inlet cooling water temperature: 30â.Outlet cooling water temperature: 35â. |
||||||
|
2. working range: |
||||||
|
The temperature range of chilled fluid is from 5â to 20â; |
||||||
|
Temperature difference between inlet and outlet cooling water is from 3â to 8â. |
||||||
|
We reserve the right to modify the above dimensions or parameters without further notice. |
||||||
Other products from this supplier
Related products from premium suppliers on EC21
Browse: Manufacturer Directory Premium Suppliers Site Map
About EC21 Contact Us Terms & Conditions Report Item Online Trading Risks Product Listing Policy
Copyright (c)1997-2026 EC21 Inc. All Rights Reserved. EC21 in KoreanChinese
Business Registry Number: 120-86-03931 | Mall order sales Registration Number: 강남-5838